Skip to content
BuildWire Calc
Pro Pro is active in this browser. Open your Pro accountPro free trial is active. Open your Pro accountPro is active but will not renew. Open your Pro account
All tools

Wire & cable

Power

Conduit & loads

Motors & gensets

Get App

Motor Circuit Breaker Calculator

Determine motor full-load amperes, branch conductor gauge, inverse time circuit breaker, and overload protection per NEC Article 430.

Pro calculator. The examples run free for everyone, with full results and steps; 3 results a month with your own numbers are free, then Pro. Always free: 9 calculators + 5 charts.

Calculates wire and electrical parameters per NEC 2023. Runs in your browser. Verify with your local code and a licensed electrician before you install.

Open on BuildWire Calc

This embed was switched off for this website. Open on BuildWire Calc

Add this tool to your siteFree embed code, no sign-up. Keep the credit link.

Embed this tool

Copy this code into your website, blog or class page. The tool runs inside your page.

Optional settings, added to the address after embed=1: &accent=0f6b5c (colour, 3 or 6 hex digits). Other parameters are ignored.

Please keep the credit link below the tool.

This motor circuit breaker calculator determines branch circuit conductor sizing, short-circuit and ground-fault protection, and overload device ratings for alternating-current electric motors per National Electrical Code Article 430. Electric motors generate extreme starting inrush currents—frequently 600 to 800 percent of full-load current—during locked-rotor acceleration. To prevent nuisance tripping when motors start, NEC 430.52 permits thermal-magnetic inverse time circuit breakers to be sized up to 250 percent of the table full-load current (FLC), or time-delay fuses up to 175 percent. Meanwhile, conductors are protected against steady running overloads by separate overload relays sized between 115 and 125 percent, while branch conductors must have an ampacity of at least 125 percent of table FLC per NEC 430.22.
Motor circuit breaker calculator example

How to use the Motor Circuit Breaker Calculator

  1. Select the motor horsepower (1/6 hp to 200 hp), the phase and the rated motor voltage (single-phase 115-230 V up to 10 hp; three-phase 200-575 V from 1/2 hp).
  2. Select the service factor / temperature-rise group: SF 1.15 or more or a marked rise of 40 °C or less (overloads at 125 %), or all other motors (115 %).
  3. Optionally enter the nameplate full-load current under More options: overloads are set from it (430.32), not from the table.
  4. Read the table full-load current (430.248 / 430.250), the minimum conductor ampacity at 125 % (430.22) and the smallest copper size at 75 °C terminals.
  5. Read the maximum inverse-time breaker (250 %) and dual-element fuse (175 %) ratings, each rounded up to the next standard size as Table 430.52(C)(1) Exception 1 allows.
  6. Check the disconnect, controller and conduit fill separately, because this calculator sizes only the conductors, breaker, fuse and overload. Confirm the result with your local code and a licensed electrician.

Example: a 10 hp, 230 V three-phase motor has a table full-load current of 28 A. The branch conductors need at least 28 × 1.25 = 35 A, which is 10 AWG copper at 75 °C terminals. The inverse-time breaker may be up to 28 × 2.5 = 70 A, and a dual-element fuse up to 28 × 1.75 = 49 A, rounded up to 50 A. If the nameplate says 26 A and the service factor is 1.15, the overload relay may be set at up to 26 × 1.25 = 32.5 A.

NEC Article 430 Rules for Sizing Motor Branch Circuits

Wiring an electric motor differs fundamentally from wiring resistive lighting or electric heating loads. A motor branch circuit separates overload protection from short-circuit and ground-fault protection.

Why NEC Table FLC Governs Conductor and Breaker Sizing

Under NEC 430.6(A)(1), engineers and electricians are strictly prohibited from using the motor nameplate current rating when sizing branch conductors, disconnect switches, and short-circuit protective devices. Instead, conductors and breakers must be sized using the standard full-load currents (FLC) published in:

  • NEC Table 430.248: Full-Load Currents in Amperes for Single-Phase AC Motors.
  • NEC Table 430.250: Full-Load Currents in Amperes for Three-Phase AC Motors.

The actual motor nameplate current is used exclusively for sizing running thermal overload protection (heaters and electronic overload relays) per NEC 430.32. This standard ensures that if a motor burns out and is replaced with a motor of identical horsepower from a different manufacturer with a lower power factor or efficiency, the installed wiring and breakers remain fully code-compliant.

Conductor Ampacity Sizing (NEC 430.22)

Conductors supplying a single motor must have an ampacity not less than 125 percent of the motor table full-load current rating per NEC 430.22: $$\text{Conductor Ampacity} \ge \text{Table FLC} \times 1.25$$

For example, a 5 HP three-phase 460V motor has a Table 430.250 FLC of 7.6 amperes. The minimum branch conductor ampacity is $7.6 \times 1.25 = 9.5$ amperes. Under standard terminal rules, 14 AWG copper wire (rated 20A at 75 °C) provides compliant ampacity.

Motor Short-Circuit and Ground-Fault Protection (NEC 430.52)

Because electric motors draw high inrush currents upon starting, standard circuit breakers would trip instantly if sized to match conductor ampacity. NEC Table 430.52 permits sizing short-circuit and ground-fault protective devices up to specific percentage limits of table FLC:

  • Inverse Time Breakers: Maximum 250% of Table FLC. If 250% does not correspond to a standard breaker size (NEC 240.6), the next higher standard rating is permitted (or up to 400% under exception rules if the motor still fails to start).
  • Dual-Element Time-Delay Fuses: Maximum 175% of Table FLC (up to 225% if needed to start).
  • Non-Time-Delay Fuses: Maximum 300% of Table FLC.

For our 7.6A motor example, multiplying by 250% yields $7.6 \times 2.50 = 19.0$ amperes. Sizing up to the next standard rating allows a 20A circuit breaker protecting a circuit wired with 14 AWG conductor. Overload relays in the motor starter protect the wire from long-term low-grade overheating.

Worked examples

InputResult
5 hp, three-phase, 460 V motor (table FLC 7.6 A)Max 20 A breaker, 15 A fuse; wire 14 AWG Cu; overload about 9.5 A (set from the nameplate current)
10 hp, three-phase, 230 V motor (table FLC 28 A)Max 70 A breaker, 50 A fuse; wire 10 AWG Cu; overload about 35 A (set from the nameplate current)
1 hp, single-phase, 115 V motor (table FLC 16 A)Max 40 A breaker, 30 A fuse; wire 14 AWG Cu; overload about 20 A (set from the nameplate current)
20 hp, three-phase, 460 V motor (table FLC 27 A)Max 70 A breaker, 50 A fuse; wire 10 AWG Cu; overload about 31.05 A (set from the nameplate current)

Calculated by the tool above; open it with the same values to see each step.

Questions, briefly answered

Common questions regarding electric motor branch circuit calculations and NEC Article 430 requirements:

Why is the circuit breaker size much larger than the wire ampacity for a motor?

Under NEC Article 430, the branch circuit breaker provides short-circuit and ground-fault protection only. High starting inrush currents require sizing the breaker up to 250% of motor full-load amperes to allow the motor to accelerate without tripping. Conductor thermal overload protection is handled downstream by thermal or electronic overload relays in the motor starter, which trip if continuous operating current exceeds 115% to 125% of nameplate rating.

Should I size motor wire using the motor nameplate or NEC tables?

Per NEC 430.6(A)(1), you must use the standard tables (Table 430.248 for single-phase and Table 430.250 for three-phase) to determine full-load current for sizing branch conductors, switches, and circuit breakers. Motor nameplate current is used only to select the thermal overload protection setting on the starter.

What is the maximum breaker size for a 10 HP 230V 3-phase motor?

From NEC Table 430.250, a 10 HP 230V 3-phase motor has a full-load current of 28 amperes. Sizing branch conductors at 125% requires an ampacity of $28 \times 1.25 = 35$ amperes: 10 AWG copper (35 A) where the terminals are rated 75 °C, 8 AWG copper where they are rated 60 °C. For inverse-time circuit breakers, Table 430.52(C)(1) permits 250%, which equals $28 \times 2.50 = 70$ amperes, so 70 A is the maximum breaker; overload protection is then set from the nameplate current.

How are motor overload heaters sized differently from the circuit breaker?

Motor overload protection guards against prolonged operating overloads that can burn out motor windings. Under NEC 430.32, thermal overloads are sized based on actual motor nameplate current (not table FLC): typically 125% of nameplate rating for motors with a service factor (SF) of 1.15 or greater, and 115% for motors with a 1.0 service factor.