Wire Size for 100 Amp Circuit

Find the copper or aluminum wire for a 100 A subpanel, garage feeder or dwelling service, and check the voltage drop for your run.

Pro calculator. The examples run free for everyone, with full results and steps; 3 results a month with your own numbers are free, then Pro. Always free: 9 calculators + 5 charts.

Assumes NEC 2023 Table 310.16: copper or aluminum, up to 3 current-carrying conductors in a raceway or cable, 30 °C ambient, 60 °C terminals for a 100 A circuit (110.14(C)), 3 % drop target; the dwelling service size follows NEC 310.12 (83 %, 75 °C); ground wire not included. Runs in your browser. Verify with your local code and a licensed electrician before you install.

Open on BuildWire Calc

This embed was switched off for this website. Open on BuildWire Calc

Add this tool to your siteFree embed code, no sign-up. Keep the credit link.

Embed this tool

Copy this code into your website, blog or class page. The tool runs inside your page.

Optional settings, added to the address after embed=1: &accent=0f6b5c (colour, 3 or 6 hex digits). Other parameters are ignored.

Please keep the credit link below the tool.

The wire size for a 100 amp subpanel or garage feeder is 1 AWG copper or 1/0 aluminum when the terminals are treated as 60 °C, which is the default for circuits of 100 A or less. Terminals listed for 75 °C allow 3 AWG copper or 1 AWG aluminum. A dwelling service rated 100 A follows a separate rule (NEC 310.12) that allows 4 AWG copper or 2 AWG aluminum. Enter the breaker, your load, the length and the conductor, and the calculator gives all of these, the voltage drop, and how far the size can run. With the starting values (80 A on 240 V over 75 ft of copper) the answer is 1 AWG with a 0.77 % drop.

How to use the 100 Amp Wire Size Calculator

  1. Keep 100 in “Breaker rating (A)”, or type the rating of your breaker or main.
  2. Enter the nameplate or calculated current in “Load current (A)”. Leave it empty to size for the full breaker rating, which is the safe choice for a subpanel feeder.
  3. Tick “Continuous load (3 hours or more)” for a charger or heater. The design current becomes 125 % of the load and must stay at or under 100 A.
  4. Pick the “Supply type” and enter “Voltage (V)”: 240 for a residential subpanel, or the line-to-line voltage for three phase, for example 208.
  5. Type the “One-way length” in ft or m, measured along the cable or conduit route from the panel to the subpanel.
  6. Choose Copper or Aluminum under “Conductor” and the “Insulation temperature rating” printed on the cable, for example 90 °C for THWN-2 or XHHW-2 in conduit (the terminal setting still caps the answer at the 60 or 75 °C column).
  7. Leave “Allowed voltage drop (%)” at 3 unless your project sets another limit.
  8. Open the advanced settings only when they apply: “Terminal temperature rating” (set 75 °C only when the breaker and the subpanel lugs are listed for it), “Ambient temperature” and the number of current-carrying conductors.
  9. Read “Recommended wire size”, “Deciding limit” and the “Dwelling service or feeder” rows, then the steps and warnings.

The example buttons load a copper subpanel, an aluminum garage feed, an EV charger, a dwelling service and a three phase feeder. “Copy result”, “Copy link” and “Print / save as PDF” keep the answer.

What size wire do I need for a 100 amp subpanel?

A subpanel fed from a 100 A breaker needs a conductor whose allowed ampacity reaches 100 A. With Auto terminals (60 °C for circuits up to 100 A, NEC 110.14(C)(1)) that is 1 AWG copper (110 A in the 60 °C column) or 1/0 aluminum (100 A). The sizes people quote, 3 AWG copper and 1 AWG aluminum, are the 75 °C column values and apply only when both ends are listed for 75 °C. Select “75 °C (listed equipment)” in the advanced terminal setting to see them.

Settings (100 A breaker, 80 A load, 240 V, 75 ft)CopperAluminum
Terminals Auto (60 °C)1 AWG1/0 AWG
Terminals listed for 75 °C3 AWG1 AWG
Dwelling service or feeder, NEC 310.124 AWG2 AWG

What size wire for a 100 amp service?

For the service or feeder that carries the whole load of a one-family dwelling, NEC 310.12 lets the conductors be 83 % of the rating: 83 A for a 100 A service. In the 75 °C column that is 4 AWG copper (85 A) or 2 AWG aluminum (90 A). The tool shows these in the “Dwelling service or feeder” rows. They do not apply to a garage or shop subpanel, which uses the breaker-rated size above. The service rows appear only when NEC 310.12 applies to your inputs: nominal 120/240 V single phase (not 208 V), a 100 to 400 A rating, a calculated load entered, conductors rated 75 °C or more, up to 3 current-carrying conductors and a 30 °C ambient. For three phase, 60 °C cable such as NM-B, more conductors, a hotter ambient or a rating outside 100-400 A, the tool says so and gives no smaller size. If your calculated load (125 % for continuous loads) is above the 83 % figure, the rows show the larger size that carries the load; with the load left empty they show no 83 % size and ask for it.

How far can you run 100 amp wire?

At an 80 A load on 240 V, 1 AWG copper reaches about 293 ft one way before the drop passes 3 %; at a full 100 A load it reaches about 234 ft. Beyond that the calculator moves up a size.

Copper unless noted, 240 VOne-way lengthResult
80 A load100 ft1 AWG, 1.03 % drop
80 A load200 ft1 AWG, 2.05 % drop
100 A load300 ft2/0 AWG, 2.42 % drop
80 A load, aluminum150 ft1/0 AWG, 2.01 % drop

The ground wire is separate: for a 100 A breaker the equipment grounding conductor is 8 AWG copper or 6 AWG aluminum, found with the equipment grounding conductor calculator.

Worked examples

InputResult
100 A breaker, 80 A load, 240 V, 75 ft, copper 75 °C1 AWG (0.769 %)
100 A breaker, 100 A load, 240 V, 30 ft, copper 75 °C1 AWG (0.384 %)
100 A breaker, 80 A load, 240 V, 40 ft, copper 75 °C1 AWG (0.41 %)
100 A breaker, 80 A load, 240 V, 150 ft, aluminum 75 °C1/0 AWG (2.01 %)
100 A breaker, 80 A load, 240 V, 40 ft, copper 60 °C1 AWG (0.41 %)

Calculated by the tool above; open it with the same values to see each step.

Questions, briefly answered

What size wire for a 100 amp subpanel?

1 AWG copper or 1/0 aluminum with Auto terminals, or 3 AWG copper and 1 AWG aluminum when the breaker and the subpanel lugs are listed for 75 °C.

What size wire for a 100 amp service?

For a one-family dwelling service, NEC 310.12 allows 4 AWG copper or 2 AWG aluminum because the conductors may be rated at 83 % of 100 A. It applies only to the dwelling service or a feeder that carries the whole dwelling load; check that your utility and inspector accept it.

Is 4 gauge wire good for 100 amps?

Only as a dwelling service or feeder under NEC 310.12 (4 AWG copper has 85 A in the 75 °C column, above the 83 A needed). As a subpanel feeder it is too small, because the conductor must carry the 100 A breaker.

Is 3 AWG enough for a subpanel on a 100 A breaker?

Yes, if the breaker and the subpanel are both listed for 75 °C and the cable is rated 75 °C or more; 3 AWG copper has 100 A in the 75 °C column. With 60 °C terminals it falls short and the answer is 1 AWG.

What size aluminum wire for 100 amps?

1/0 aluminum with Auto terminals, 1 AWG with 75 °C listed equipment, and 2 AWG as a dwelling service. Aluminum needs lugs marked AL/CU.

How far can I run 1 gauge wire at 100 amps?

About 234 ft one way at 240 V with a full 100 A load and a 3 % target; the “Longest run of the recommended size” row updates with your own load.

What size ground wire for a 100 amp breaker?

8 AWG copper or 6 AWG aluminum under NEC Table 250.122. It is not included in the wire size above.

What size wire for a detached garage on a 100 A feeder?

The same breaker-rated size: 1 AWG copper, or 1/0 aluminum for a run of about 150 ft (2.0 % drop at 80 A), unless the listed 75 °C equipment allows the smaller sizes. A feeder to another building also needs its own grounding electrode.