Wire Size for 125 Amp Circuit

Find the copper or aluminum wire for a 125 A subpanel, service or feeder, and check the voltage drop for a long run.

Pro calculator. The examples run free for everyone, with full results and steps; 3 results a month with your own numbers are free, then Pro. Always free: 9 calculators + 5 charts.

Assumes NEC 2023 Table 310.16: copper or aluminum, up to 3 current-carrying conductors in a raceway or cable, 30 °C ambient, 75 °C column above 100 A with 14 to 1 AWG held to 60 °C (110.14(C)); the dwelling service size follows NEC 310.12 (83 %, 75 °C); 3 % drop target; ground wire not included. Runs in your browser. Verify with your local code and a licensed electrician before you install.

Open on BuildWire Calc

This embed was switched off for this website. Open on BuildWire Calc

Add this tool to your siteFree embed code, no sign-up. Keep the credit link.

Embed this tool

Copy this code into your website, blog or class page. The tool runs inside your page.

Optional settings, added to the address after embed=1: &accent=0f6b5c (colour, 3 or 6 hex digits). Other parameters are ignored.

Please keep the credit link below the tool.

The wire size for a 125 amp breaker is 1/0 AWG copper or 2/0 aluminum with Auto terminals. Copper can go down to 1 AWG only when the breaker and equipment are listed for 75 °C. A dwelling service or feeder that carries the whole home load follows a separate rule (NEC 310.12, 83 %) and allows 2 AWG copper or 1/0 aluminum for a 100 A load. Enter the breaker, your load, the length and the conductor, and the calculator gives all of these, the voltage drop, and how far the size can run. With the starting values (100 A on 240 V over 75 ft of copper) the answer is 1/0 AWG with a 0.76 % drop.

How to use the 125 Amp Wire Size Calculator

  1. Keep 125 in “Breaker rating (A)”, or type the rating of your breaker or main.
  2. Enter the nameplate or calculated current in “Load current (A)”. The starting load is 100 A. Leave it empty to size for the full 125 A.
  3. Tick “Continuous load (3 hours or more)” for a charger or heater. The design current becomes 125 % of the load and must stay at or under 125 A.
  4. Pick the “Supply type” and enter “Voltage (V)”: 240 for a residential subpanel or service, or the line-to-line voltage for three phase, for example 208.
  5. Type the “One-way length” in ft or m, measured along the route from the main to the subpanel.
  6. Choose Copper or Aluminum under “Conductor” and the “Insulation temperature rating” printed on the cable, (the terminal setting still caps the answer at the 60 or 75 °C column).
  7. Leave “Allowed voltage drop (%)” at 3 unless your project sets another limit.
  8. Open the advanced settings only when they apply: “Terminal temperature rating” (set “75 °C (listed equipment)” only when the breaker and the lugs are listed for it), “Ambient temperature” and the number of current-carrying conductors.
  9. Read “Recommended wire size”, “Deciding limit”, the “Dwelling service or feeder” rows and “Longest run of the recommended size”, then the steps and warnings.

The example buttons load a 100 A run at 75 ft, a 125 A run at 30 ft, a 100 A continuous load at 40 ft, an aluminum 150 ft run and a copper run with 60 °C terminals at 40 ft.

What size wire do I need for a 125 amp breaker?

A 125 A breaker needs a conductor whose allowed ampacity reaches 125 A. For circuits above 100 A, Auto terminals use the 75 °C column, so the answer is 1/0 AWG copper (150 A) or 2/0 aluminum (135 A). 1 AWG copper has 130 A in the 75 °C column, but Auto terminals hold it to the 60 °C column (110 A), which is too small for 125 A. It fits only when the equipment is listed for 75 °C: select “75 °C (listed equipment)” to get 1 AWG copper. Aluminum stays at 2/0 either way.

Settings (125 A breaker, 100 A load, 240 V, 75 ft)CopperAluminum
Terminals Auto1/0 AWG2/0 AWG
Terminals listed for 75 °C1 AWG2/0 AWG
Dwelling service or feeder, NEC 310.122 AWG1/0 AWG

What size wire for a 125 amp service?

For the service or feeder that carries the whole load of a one-family dwelling, NEC 310.12 lets the conductors be 83 % of the rating: 83 % of 125 A is 103.75 A. In the 75 °C column that is 2 AWG copper or 1/0 aluminum for the default 100 A load. If the calculated load is 125 A, the rows show 1 AWG copper (130 A) or 2/0 aluminum (135 A) instead. With the load left empty they show no 83 % size.

The dwelling size applies only to the service or feeder that carries the whole dwelling load, nominal 120/240 V single phase (not 208 V), conductors rated 75 °C or more, up to 3 current-carrying conductors and a 30 °C ambient. Outside those conditions the tool says so and gives no smaller size. It does not apply to a garage or shop subpanel, which uses the breaker-rated size above. Check that your utility and inspector accept it.

How far can you run 125 amp wire?

At a full 125 A load on 240 V, 1/0 AWG copper reaches about 236 ft one way before the drop passes 3 %. At a 100 A load it reaches about 295 ft. Beyond that the calculator moves up a size.

Copper unless noted, 240 VOne-way lengthResult
100 A load75 ft1/0 AWG, 0.76 % drop
100 A load100 ft1/0 AWG, 1.02 % drop
125 A load (full breaker)75 ft1/0 AWG, 0.95 % drop
125 A load200 ft1/0 AWG, 2.54 % drop
125 A load300 ft3/0 AWG, 2.40 % drop
125 A load400 ft4/0 AWG, 2.53 % drop
100 A load, aluminum150 ft2/0 AWG, 1.99 % drop

A 100 A continuous load has a design current of 125 %, or 125 A, so it needs 1/0 AWG copper on this breaker. The dwelling service rows then show 1 AWG copper or 2/0 aluminum.

The ground wire is separate. For a 125 A breaker the equipment grounding conductor is 6 AWG copper or 4 AWG aluminum (NEC Table 250.122, 100 to 200 A), found with the equipment grounding conductor calculator.

Worked examples

InputResult
125 A breaker, 100 A load, 240 V, 75 ft, copper 75 °C1/0 AWG (0.762 %)
125 A breaker, 125 A load, 240 V, 30 ft, copper 75 °C1/0 AWG (0.381 %)
125 A breaker, 100 A load, 240 V, 40 ft, copper 75 °C1/0 AWG (0.406 %)
125 A breaker, 100 A load, 240 V, 150 ft, aluminum 75 °C2/0 AWG (1.99 %)
125 A breaker, 100 A load, 240 V, 40 ft, copper 60 °C1/0 AWG (0.406 %)

Calculated by the tool above; open it with the same values to see each step.

Questions, briefly answered

What size wire for a 125 amp breaker or subpanel?

1/0 AWG copper or 2/0 aluminum with Auto terminals. A 125 A subpanel fed from a 125 A breaker uses the same size. With a 100 A load over 75 ft, 1/0 copper gives a 0.76 % drop.

What size wire for a 125 amp service?

Under NEC 310.12 a one-family dwelling service can use 83 % of 125 A (103.75 A): 2 AWG copper or 1/0 aluminum for a 100 A load, or 1 AWG copper or 2/0 aluminum for a 125 A calculated load. Use this only for the service or feeder that carries the whole dwelling load.

Can I use 1 AWG copper on a 125 amp breaker?

Only when the breaker and the equipment lugs are listed for 75 °C. 1 AWG copper is 130 A in the 75 °C column but only 110 A in the 60 °C column that Auto terminals use. Select “75 °C (listed equipment)” to see it.

What size aluminum wire for 125 amps?

2/0 aluminum with Auto terminals, which is rated 135 A in the 75 °C column. For a dwelling service under NEC 310.12, 1/0 aluminum is enough for a 100 A load. Aluminum needs lugs marked AL/CU.

How far can 1/0 copper run at 125 amps?

About 236 ft one way at a full 125 A load on 240 V with a 3 % target, or about 295 ft at a 100 A load. At 200 ft and 125 A the drop is 2.54 %; at 300 ft the answer moves to 3/0 AWG (2.40 %).

What about a 100 amp continuous load on a 125 amp breaker?

The design current is 125 %, or 125 A, so the answer is 1/0 AWG copper. The dwelling service rows show 1 AWG copper or 2/0 aluminum for that design load.

What size ground wire for a 125 amp breaker?

6 AWG copper or 4 AWG aluminum under NEC Table 250.122 (100 to 200 A). It is not included in the wire size above.