Wire Size for 40 Amp Circuit

Find the copper or aluminum wire for a 40 amp breaker and check the voltage drop for your run length.

Pro calculator. The examples run free for everyone, with full results and steps; 3 results a month with your own numbers are free, then Pro. Always free: 9 calculators + 5 charts.

Assumes NEC 2023 Table 310.16: copper or aluminum, up to 3 current-carrying conductors in a raceway or cable, 30 °C ambient, 60 °C terminals for a 40 A circuit (110.14(C)), 3 % drop target; ground wire not included. Runs in your browser. Verify with your local code and a licensed electrician before you install.

Open on BuildWire Calc

This embed was switched off for this website. Open on BuildWire Calc

Add this tool to your siteFree embed code, no sign-up. Keep the credit link.

Embed this tool

Copy this code into your website, blog or class page. The tool runs inside your page.

Optional settings, added to the address after embed=1: &accent=0f6b5c (colour, 3 or 6 hex digits). Other parameters are ignored.

Please keep the credit link below the tool.

The wire size for a 40 amp breaker is 8 AWG copper or 6 AWG aluminum when the terminals are treated as 60 °C, which is how circuits of 100 A or less are judged. Enter the breaker, your real load and the run length, and the calculator checks two limits: the wire’s allowed ampacity must reach the breaker rating, and the voltage drop over the one-way run must stay inside your target. With its starting values (a 32 A load on 240 V over 50 ft of copper) the answer is 8 AWG with a 1.04 % drop. The result names the deciding limit, shows copper and aluminum side by side, and gives the longest run of the recommended size.

How to use the 40 Amp Wire Size Calculator

  1. Keep 40 in “Breaker rating (A)”, or type the rating printed on your breaker.
  2. Enter the nameplate or calculated current in “Load current (A)”. Leave it empty and the wire is sized for the full 40 A breaker rating. A 32 A load is the usual size for a 40 A EV charger or hot tub.
  3. Tick “Continuous load (3 hours or more)” for an EV charger, a heat pump or a spa heater. The design current then becomes 125 % of the load, and the tool warns when that is above the breaker.
  4. Pick the “Supply type” and enter “Voltage (V)”: 240 for most 40 A residential circuits, or the line-to-line voltage for three phase.
  5. Type the “One-way length” in ft or m, measured along the cable route from the panel to the load.
  6. Choose Copper or Aluminum under “Conductor” and the “Insulation temperature rating” printed on the cable, for example 60 °C for NM-B or 90 °C for THHN.
  7. Leave “Allowed voltage drop (%)” at 3 unless your project sets another limit.
  8. Open the advanced settings only when they apply: “Terminal temperature rating”, “Ambient temperature” and “Current-carrying conductors in the raceway or cable”.
  9. Read “Recommended wire size” and “Deciding limit”, then the steps and warnings below the result.

The example buttons load an EV charger, a small range, a heat pump, an aluminum garage subpanel and a hot tub. “Copy result”, “Copy link” and “Print / save as PDF” keep the answer, and Reset restores the starting values.

What size wire do I need for a 40 amp breaker?

With the terminal setting left on Auto, the answer is 8 AWG copper or 6 AWG aluminum. Copper 8 AWG has exactly 40 A in the 60 °C column of NEC Table 310.16, which matches the breaker. Aluminum 8 AWG has only 35 A there, so aluminum moves up to 6 AWG. A long run can still push either size up.

The calculator checks in this order:

  1. The conductor must be protected by the breaker, so its allowed ampacity has to be at least 40 A (NEC 240.4 and 310.16).
  2. The insulation column gives the starting value; the ambient factor (310.15(B)(1)) and the factor for more than three current-carrying conductors (310.15(C)(1)) reduce it.
  3. The terminal column caps the result: circuits of 100 A or less use the 60 °C column unless the equipment is listed for 75 °C (110.14(C)(1)).
  4. Voltage drop at your load current is checked last, and the larger of the two sizes wins.

How far can you run 40 amp wire?

At a 32 A load on 240 V, 8 AWG copper reaches about 144 ft one way before the drop passes 3 %. At a full 40 A load it reaches about 115 ft. Past those distances the tool moves up a size because of voltage drop, not ampacity.

Copper, 240 V, 3 % targetOne-way lengthResult
32 A load100 ft8 AWG, 2.08 % drop
32 A load200 ft6 AWG, 2.61 % drop (8 AWG would drop 4.2 %)
40 A load100 ft8 AWG, 2.60 % drop
40 A load150 ft6 AWG, 2.45 % drop

At 120 V the same 50 ft drops 2.6 % instead of 1.3 % with a 40 A load, so voltage matters for distance but not for the ampacity answer.

Does a 40 amp EV charger or hot tub need bigger wire?

A charger or spa that draws 32 A continuously needs 32 × 125 % = 40 A, which fits a 40 A breaker, and the wire answer stays 8 AWG copper at 60 ft (1.25 % drop). The ground wire is separate: the equipment grounding conductor for a 40 A breaker is 10 AWG copper or 8 AWG aluminum, found with the equipment grounding conductor calculator.

Worked examples

InputResult
40 A breaker, 32 A load, 240 V, 50 ft, copper 75 °C8 AWG (1.04 %)
40 A breaker, 40 A load, 240 V, 30 ft, copper 75 °C8 AWG (0.779 %)
40 A breaker, 32 A load, 240 V, 40 ft, copper 75 °C8 AWG (0.831 %)
40 A breaker, 32 A load, 240 V, 150 ft, aluminum 75 °C4 AWG (2.03 %)
40 A breaker, 32 A load, 240 V, 40 ft, copper 60 °C8 AWG (0.831 %)

Calculated by the tool above; open it with the same values to see each step.

Questions, briefly answered

What size wire for a 40 amp breaker?

8 AWG copper or 6 AWG aluminum with the Auto terminal setting. Both reach 40 A in the 60 °C column, which is the column that applies to circuits of 100 A or less.

Is 10 gauge wire enough for 40 amps?

No. 10 AWG copper carries 30 A in the 60 °C column and 35 A in the 75 °C column, so it is below a 40 A breaker. NEC 240.4(D) also limits 10 AWG copper to a 30 A breaker.

Can I use 8 AWG aluminum on a 40 amp breaker?

Not with 60 °C terminals: aluminum 8 AWG has 35 A there. It reaches 40 A only in the 75 °C column, which counts only when the breaker and the load equipment are listed for 75 °C; the “75 °C” terminal setting shows it.

What wire size for a 40 amp 240 volt circuit?

The same 8 AWG copper or 6 AWG aluminum. Voltage changes the drop, not the ampacity: 8 AWG copper at 32 A over 100 ft drops 2.08 % on 240 V and twice as much on 120 V.

How far can I run 8 gauge wire on a 40 amp circuit?

About 144 ft one way at a 32 A load and 115 ft at 40 A, both at 240 V with a 3 % target. The row “Longest run of the recommended size” updates with your load.

What size wire for a 40 amp EV charger?

An EV charger rated 32 A is a continuous load, 32 A × 125 % = 40 A, so a 40 A breaker with 8 AWG copper works for runs up to about 144 ft at 3 % drop.

Can I run 40 amps on 12 gauge wire?

No. NEC 240.4(D) limits 12 AWG copper to a 20 A breaker and 12 AWG carries 25 A in the 75 °C column.

Is 3% voltage drop a requirement?

No. The 3 % for a branch circuit and 5 % in total are advice from informational notes in the NEC. You can set any target in “Allowed voltage drop (%)”.