Wire Size for 70 Amp Circuit

Find the copper or aluminum wire for a 70 A subpanel, spa or shop feeder and check the voltage drop for your run.

Pro calculator. The examples run free for everyone, with full results and steps; 3 results a month with your own numbers are free, then Pro. Always free: 9 calculators + 5 charts.

Assumes NEC 2023 Table 310.16: copper or aluminum, up to 3 current-carrying conductors in a raceway or cable, 30 °C ambient, 60 °C terminals for a 70 A circuit (110.14(C)), 3 % drop target; the 83 % dwelling service rule (310.12) does not apply below 100 A; ground wire not included. Runs in your browser. Verify with your local code and a licensed electrician before you install.

Open on BuildWire Calc

This embed was switched off for this website. Open on BuildWire Calc

Add this tool to your siteFree embed code, no sign-up. Keep the credit link.

Embed this tool

Copy this code into your website, blog or class page. The tool runs inside your page.

Optional settings, added to the address after embed=1: &accent=0f6b5c (colour, 3 or 6 hex digits). Other parameters are ignored.

Please keep the credit link below the tool.

The wire size for a 70 amp breaker is 4 AWG copper or 2 AWG aluminum when the terminals are treated as 60 °C, which is the default for circuits up to 100 A. Terminals listed for 75 °C keep 4 AWG copper and allow 3 AWG aluminum. Enter the breaker, your load, the length and the conductor, and the calculator gives the size, the voltage drop, and how far that size can run. With the starting values (56 A on 240 V over 60 ft of copper) the answer is 4 AWG with a 0.86 % drop. Change the length and the drop updates, so you can see where 4 AWG stops being enough and the next size up is worth the cost.

How to use the 70 Amp Wire Size Calculator

  1. Keep 70 in “Breaker rating (A)”, or type the rating of your breaker.
  2. Enter the nameplate or calculated current in “Load current (A)”. The starting load is 56 A, which is 80 % of 70 A. Leave it empty to size for the full 70 A.
  3. Tick “Continuous load (3 hours or more)” for a spa heater, a charger or another long-running load. The design current becomes 125 % of the load and must stay at or under 70 A.
  4. Pick the “Supply type” and enter “Voltage (V)”: 240 for a subpanel or spa feeder. For three phase, use the line-to-line voltage.
  5. Type the “One-way length” in ft or m, measured along the cable or conduit route from the main panel to the subpanel or load.
  6. Choose Copper or Aluminum under “Conductor” and the “Insulation temperature rating” printed on the cable (the terminal setting still caps the answer at the 60 or 75 °C column).
  7. Leave “Allowed voltage drop (%)” at 3 unless your project sets another limit.
  8. Open the advanced settings only when they apply: “Terminal temperature rating” (set 75 °C only when the breaker and the subpanel lugs are listed for it), “Ambient temperature” and the number of current-carrying conductors.
  9. Read “Recommended wire size”, “Deciding limit” and “Longest run of the recommended size”, then the steps and warnings.

The example buttons load a copper subpanel at 56 A and 60 ft, a 70 A feeder at 30 ft, a 40 ft run, an aluminum 150 ft run and a copper run with 60 °C terminals.

What size wire do I need for a 70 amp breaker?

A 70 A breaker needs a conductor whose allowed ampacity reaches 70 A. With Auto terminals (60 °C for circuits up to 100 A, NEC 110.14(C)(1)) that is 4 AWG copper (70 A in the 60 °C column) or 2 AWG aluminum. If the breaker and the lugs are listed for 75 °C, copper stays at 4 AWG (85 A in the 75 °C column, and no smaller size reaches 70 A) and aluminum drops to 3 AWG (75 A). Select “75 °C (listed equipment)” in the advanced terminal setting to see the 75 °C result.

Settings (70 A breaker, 56 A load, 240 V, 60 ft)CopperAluminum
Terminals Auto (60 °C)4 AWG2 AWG
Terminals listed for 75 °C4 AWG3 AWG

A 56 A load is 80 % of 70 A, the most a continuous load can be on a 70 A breaker, because the 125 % rule sets the design current at 70 A.

The ground wire is separate. For a 70 A breaker the equipment grounding conductor is 8 AWG copper or 6 AWG aluminum (NEC Table 250.122, 60 to 100 A), found with the equipment grounding conductor calculator.

How far can you run 70 amp wire?

With a 56 A load on 240 V, 4 AWG copper reaches about 209 ft one way before the drop passes 3 %. At a full 70 A load it reaches about 167 ft. Beyond that the calculator moves up a size.

Copper unless noted, 240 VOne-way lengthResult
56 A load60 ft4 AWG, 0.86 % drop
56 A load100 ft4 AWG, 1.44 % drop
56 A load200 ft4 AWG, 2.88 % drop
70 A load150 ft4 AWG, 2.70 % drop
70 A load250 ft2 AWG, 2.83 % drop
56 A load, aluminum100 ft2 AWG, 1.49 % drop

Does the 83 % dwelling service rule apply at 70 amps?

No. The dwelling service size under NEC 310.12 is for 100 to 400 A services. A 70 A subpanel, spa or shop feeder uses the breaker-rated size above.

Worked examples

InputResult
70 A breaker, 56 A load, 240 V, 60 ft, copper 75 °C4 AWG (0.863 %)
70 A breaker, 70 A load, 240 V, 30 ft, copper 75 °C4 AWG (0.539 %)
70 A breaker, 56 A load, 240 V, 40 ft, copper 75 °C4 AWG (0.575 %)
70 A breaker, 56 A load, 240 V, 150 ft, aluminum 75 °C2 AWG (2.23 %)
70 A breaker, 56 A load, 240 V, 40 ft, copper 60 °C4 AWG (0.575 %)

Calculated by the tool above; open it with the same values to see each step.

Questions, briefly answered

What size wire for a 70 amp breaker?

4 AWG copper or 2 AWG aluminum with Auto terminals (60 °C column). With the breaker and lugs listed for 75 °C, copper stays at 4 AWG and aluminum is 3 AWG.

What size wire for a 70 amp subpanel?

The same breaker-rated size: 4 AWG copper or 2 AWG aluminum. At a 56 A load (80 % of 70 A) and 60 ft, 4 AWG copper gives a 0.86 % drop.

Is 4 gauge wire good for 70 amps?

Yes, for a 70 A breaker with Auto terminals: 4 AWG copper is rated 70 A in the 60 °C column. A 56 A load over 200 ft still stays under 3 % (2.88 %).

What size aluminum wire for 70 amps?

2 AWG aluminum with Auto terminals, or 3 AWG aluminum when the equipment is listed for 75 °C. At a 56 A load over 100 ft, 2 AWG aluminum gives a 1.49 % drop and reaches about 201 ft before the drop passes 3 %. Aluminum needs lugs marked AL/CU.

How far can 4 AWG copper run at 70 amps?

About 209 ft one way at a 56 A load, or about 167 ft at a full 70 A load, both at a 3 % target. For 250 ft at a 70 A load, the answer is 2 AWG (2.83 %).

Does the dwelling service rule change a 70 amp feeder?

No. NEC 310.12 covers 100 to 400 A dwelling services, so a 70 A feeder is sized from the breaker and its terminal rating.

What size ground wire for a 70 amp breaker?

8 AWG copper or 6 AWG aluminum under NEC Table 250.122 (60 to 100 A). It is not included in the wire size above.